Multi Function Testers

6016
The KEW 6016 Multi-Function tester performs 10 functions
in one instrument.
Continuity tester
Insulation resistance tester
Loop impedance tester
PSC tester
PFC tester
RCD tester
Earth tester
Phase rotation tester
Voltage measurement
Frequency measurement

6010B
6010B
Continuity: 20/200Ω, 200mA Test Current
Insulation: 500/1000V, 20/200MΩ, 1mA Rated Test Current
Loop Impedance: 20/2000Ω, 15mA Test Current at 2000Ω (No RCD Trip)
RCD: 10/30/100/300/500mA x1/2, x1, Fast Trip(40ms), DC, Auto Ramp
Test of a large kind of RCD's:
Standard, Selective, AC and A (DC sensitive breakers)
Uc (Contact Voltage): 100V
Designed to IEC 61010-1, IEC 61557
Data Memory: 300 measured results
The stored data can be transferred to PC via Optical Adaptor Model 8212-USB or 8212-RS232C.

6010A
6010A
Continuity and Insulation Testing
Live circuit warning LED:
Immediate illumination of a warning lamp if the circuit under test is live
Auto Discharge:
Allows fast and safe discharge of electrical energy stored in capacitive circuits following testing
Integral overload protection on internal continuity and insulation test circuitry
Autoranging
500V DC test voltage for insulation tests
200mA short circuit current on continuity ranges
   
Loop and RCD Testing
Wiring connection check LED's:
Immediate indication if wiring of circuit under test is correct
Overheat Protection:
Rapid detection of overheating of internal circuitry,display of warning signal to user and automatic halting of measurement
Supply Voltage Indication:
Can display supply voltage value in loop impedance mode
Low Current Loop Impedance Test:
Short duration low test current will prevent tripping of many passive RCDs
Auto Data Hold:
Retains displayed reading for set period following test
Phase Angle Selection:
Selection of test current from +ve or -ve half cycle of waveform can prevent tripping of polarized type RCDs

6011A
6011A
Complies with IEC 61557
Designed to IP 54 Rating
Live circuit and wiring connection check LED's
Triple ranges insulation tests at 250, 500 and 1000V
Triple range loop and PSC tests 15mA test current at 200Ω/2000Ω range (No RCD Trip)
Phase angle selection on RCD ranges
Polarity switch for continuity tests
Auto-null facility for continuity tests
Earth probe for loop impedance testing on extraneous metalwork
Contact Voltage Reading
Test of a large kind of RCD's:
Standard, Selective, AC and A (DC sensitive breakers)

6018
6018
Designed to meet IEC 61010-1 CAT.III 600V
Test leads with remote control switch.
(For insulation&Simplified Earth Test)
Back light function.
Color coded scales and range switch position for easy reading.
Automatic warning when resistance of auxiliary earth spikes is in excess of tolerance.
Can be hung around the neck for both hand’s operation.